Introduction
When specifying or purchasing a low voltage (LV) switchboard, engineers often encounter three common internal separation classifications: Form 3b, Form 4a and Form 4b.
These designations do not refer to different switchboard models. They describe how the internal components of a switchboard are separated to reduce the risk of accidental contact between electrical compartments and make maintenance work easier to manage.
In simple terms, internal separation uses barriers, partitions or other suitable construction methods to separate busbars, functional units and cable connection terminals.
The main difference between Form 3b, Form 4a and Form 4b is how the terminals for external conductors are separated from other functional units and where they are located within the switchboard.
These configurations are commonly considered in industrial power distribution, data centers, oil and gas facilities, mining operations and large infrastructure projects.
Understanding the differences helps engineers select the appropriate switchboard structure according to project specifications, maintenance requirements and installation conditions.
This article explains the three forms under IEC 61439, including their structural characteristics, typical applications and selection considerations.
1. What Is Internal Separation in LV Switchboards?
A typical low voltage switchboard contains three main areas:
1. Busbar Compartment: Contains the main and distribution busbars, which distribute electrical power to individual circuits.
2. Functional Unit Compartment: Houses circuit breakers, contactors, protection devices and other components responsible for controlling and protecting individual circuits.
3. External Conductor Terminal Area: Provides connection points for incoming and outgoing cables that connect the switchboard to external electrical equipment.
Without appropriate internal separation, these areas may have a greater risk of accidental contact or fault propagation between different sections.
By installing suitable barriers, partitions or separate compartments, the manufacturer can divide the switchboard into clearly defined functional areas.
IEC 61439 describes different forms of internal separation, including Forms 1, 2, 3 and 4, with additional subcategories.
The basic principles are:
- Form 3: Busbars are separated from all functional units, and individual functional units are separated from one another. The external conductor terminals are also separated from the functional units.
- Form 4: Provides the Form 3 separation requirements, with additional separation between the external conductor terminals associated with different functional units.
Form 3b, Form 4a and Form 4b are frequently specified in industrial low voltage switchboard projects.
It is important to understand that a higher Form number does not automatically mean better performance in every safety category. The classification describes the internal separation arrangement. It does not define short-circuit withstand capacity, IP protection rating or overall electrical performance.
2. Form 3b: Separation of Busbars, Functional Units and External Terminals
Form 3b is a commonly used internal separation arrangement for low voltage switchboards.
It separates the main busbar system from the functional units and provides separation between individual functional units.
Its main characteristics include:
- Main busbars are separated from all functional units.
- Individual functional units are separated from one another.
- External conductor terminals are separated from the associated functional units.
- External conductor terminals are separated from the main busbar system.
- Terminals belonging to different functional units are not required to be separated from one another.
In practical terms, each circuit's main electrical equipment is installed in a separate functional unit. However, the outgoing cable terminals from different circuits may share a common cable connection compartment.
For example, consider an LV switchboard with several outgoing feeders, each equipped with an individual MCCB (Molded Case Circuit Breaker).
In a Form 3b arrangement, the MCCBs are installed in separate functional compartments. However, the cable connection terminals for multiple outgoing feeders may be located in the same common cable compartment without individual partitions between them.
This arrangement provides a practical level of internal separation while maintaining reasonable space utilization and manufacturing cost.
Typical applications include:
- General industrial power distribution systems.
- Factory power distribution switchboards.
- Commercial building electrical distribution.
- Projects requiring separation between functional units but not individual isolation of every outgoing terminal.

Schematic diagram of Schneider enclosure (Form 3b construction)
3. Form 4a: Additional Separation Between Different Circuit Terminals
Form 4a provides additional separation between the external conductor terminals associated with different functional units.
The main difference from Form 3b is that the terminals of different outgoing circuits are also separated from one another.
Its main characteristics include:
- Busbars are separated from all functional units.
- Individual functional units are separated from one another.
- External conductor terminals associated with different circuits are separated.
- External conductor terminals are located in the same compartment as their associated functional unit.
The last point is particularly important.
Form 4a does not place every cable terminal in a separate compartment away from its corresponding functional unit. Instead, the terminals remain within the same compartment as the associated circuit equipment, while terminals belonging to different circuits are separated from one another.
For example, consider an LV switchboard with three outgoing circuits:
- Circuit 1: MCCB + outgoing cable terminals.
- Circuit 2: MCCB + outgoing cable terminals.
- Circuit 3: MCCB + outgoing cable terminals.
In a Form 4a arrangement, each circuit breaker and its associated cable terminals are located within the same functional compartment. Partitions separate the different circuits from one another.
This arrangement helps reduce the risk of accidental contact with adjacent circuit terminals during inspection and maintenance.
Typical applications include:
- Industrial power distribution systems with higher maintenance requirements.
- Continuous production facilities.
- Large commercial building electrical systems.
- Projects requiring separation between terminals belonging to different outgoing circuits.
4. Form 4b: Separate Compartments for External Conductor Terminals
Form 4b is another internal separation arrangement under Form 4.
Compared with Form 4a, it provides a different layout for the external conductor terminals.
Its main characteristics include:
- Busbars are separated from all functional units.
- Individual functional units are separated from one another.
- External conductor terminals associated with different functional units are separated.
- External conductor terminals are not located in the same compartment as their associated functional units.
- Terminals are installed in individual, separate, enclosed and protected spaces or compartments.
In simple terms, Form 4a places the circuit breaker and its associated cable terminals in the same compartment, while Form 4b places them in separate compartments.
For example, when maintenance personnel need to inspect an outgoing cable connection, the separate terminal compartment in a Form 4b arrangement provides a clearly defined connection area away from the associated functional unit.
This design can make the internal layout easier to manage when independent terminal compartments are specifically required by the project.
One important technical point: Form 4b requires separation between terminals associated with different functional units. However, the external conductors themselves are not necessarily required to be separated from one another. The actual cable routing and compartment arrangement must comply with the applicable standard and manufacturer's design.
Typical applications include:
- Industrial projects with strict internal separation requirements.
- Large energy and infrastructure projects.
- Power distribution systems requiring separate cable termination compartments.
- Projects where the technical specification explicitly requires Form 4b construction.
Form 4b generally requires more internal partitions and compartment space. This can increase switchboard dimensions, design complexity and manufacturing costs.

Schematic diagram of Schneider enclosure (Form 4b construction)
5. Form 3b vs Form 4a vs Form 4b: Key Differences
| Comparison Item | Form 3b | Form 4a | Form 4b |
|---|---|---|---|
| Busbars separated from functional units | Yes | Yes | Yes |
| Individual functional units separated from one another | Yes | Yes | Yes |
| External conductor terminals separated from functional units | Yes | Within the associated functional unit compartment | In separate compartments |
| External conductor terminals separated from busbars | Yes | Yes | Yes |
| Terminals of different functional units separated from one another | Not required | Yes | Yes |
| Terminals in the same compartment as associated functional unit | Not applicable | Yes | No |
| Separate terminal compartments | Not individually required | Not required | Yes |
| Structural complexity | Relatively low | Higher | Generally highest |
| Space requirements | Relatively compact | Larger | Generally largest |
Note: Separation refers to compliance with the applicable internal separation requirements. It does not mean that every compartment must use a completely enclosed metal barrier. Suitable partitions, insulating barriers and equipment enclosures may be used depending on the verified design,contcat us now!
6. How Should You Choose Between Form 3b, Form 4a and Form 4b?
There is no single internal separation form that is suitable for every LV switchboard project.
Engineers should consider the equipment application, maintenance procedures, personnel access and project technical specifications before selecting a configuration.
Choose Form 3b: Balance Separation and Cost
For conventional industrial power distribution systems, Form 3b may be suitable when the project requires separation between busbars and functional units but does not require individual separation between every outgoing circuit terminal.
It provides a practical internal arrangement while avoiding unnecessarily complex compartment structures.
Choose Form 4a: Improve Separation Between Circuit Terminals
If the project requires terminals from different outgoing circuits to be separated, while allowing each terminal set to remain in the same compartment as its associated functional unit, Form 4a is a suitable option.
This configuration is particularly relevant when maintenance access and separation between adjacent circuits are important considerations.
Choose Form 4b: Require Independent Terminal Compartments
If the project specification requires external conductor terminals to be located separately from their associated functional units, with individual enclosed terminal compartments, Form 4b should be considered.
Before finalizing the design, engineers should check the overall cabinet dimensions, cable entry arrangement, terminal access space and manufacturing cost.
For mining, utility infrastructure and large industrial projects, the required form should be determined by the owner's technical specification and applicable standards rather than the industry name alone.
7. What Technical Parameters Should You Check When Purchasing LV Switchboards?
Besides Form 3b, Form 4a and Form 4b, buyers and engineers should verify several other technical parameters when purchasing low voltage switchboards.
1. Rated Voltage: Confirm the system operating voltage, such as 400 V, 415 V or 690 V.
2. Rated Current: Check the rated current of the main busbars and individual functional units.
3. Short-Time Withstand Current: Confirm the short-circuit current and duration that the switchboard busbar system is designed to withstand.
4. IP Protection Rating: Select the required enclosure protection level according to the installation environment, such as IP31, IP42 or IP54.
5. Internal Separation Form: Clearly specify whether Form 3b, Form 4a or Form 4b is required.
6. Cable Entry: Confirm top or bottom cable entry and the available cable termination space.
7. Circuit Breaker Configuration: Specify whether ACBs, MCCBs or other protection devices are required.
8. Standard Compliance: Confirm that the complete assembly has undergone the applicable design verification and routine verification in accordance with the relevant edition of IEC 61439 or the GB/T 7251 series.
An important point: IP54 and Form 4b are two independent technical classifications.
A Form 3b switchboard can also be designed to achieve IP54 protection, depending on its enclosure construction. Similarly, a Form 4b switchboard should not automatically be assumed to have an IP54 rating.
Internal separation also does not replace design verification for short-circuit withstand, temperature rise or other required performance characteristics.
Conclusion
The main difference between Form 3b, Form 4a and Form 4b lies in the internal separation arrangement of low voltage switchboards, particularly how external conductor terminals are separated and positioned relative to their associated functional units.
Form 3b separates the busbars, functional units and external conductor terminal areas. It is a practical solution for conventional industrial power distribution.
Form 4a provides additional separation between terminals belonging to different circuits, while keeping each terminal set in the same compartment as its associated functional unit.
Form 4b places the external conductor terminals in separate compartments from their associated functional units, making it suitable for projects that specifically require independent terminal spaces.
When selecting an LV switchboard, engineers should consider project specifications, maintenance procedures, electrical ratings and installation conditions rather than simply choosing the highest Form number.
Funator supplies Schneider Electric low voltage distribution equipment and multi-brand electrical components, including PrismaSeT and Okken switchboard solutions.
Our team can support product selection, technical document review and project quotations based on your single-line diagram, rated current, short-circuit withstand requirements, internal separation form and installation conditions.
If you are sourcing Form 3b, Form 4a or Form 4b low voltage switchboards, contact Funator with your project specifications or single-line diagram to discuss suitable configurations and obtain a quotation.