Medium Voltage Switchgear

Schneider GM AirSeT SF6-Free Primary MV GIS Switchgear

SF₆-free primary MV switchgear using pure air insulation and vacuum switching — future-proof for grids moving away from fluorinated gases.

WhatsApp

Product Overview

Schneider GM AirSeT Pure air insulation combined with vacuum interruption for primary distribution up to 36 kV. Zero greenhouse gas emissions (GWP < 1), full compliance with IEC 62271-200 type testing, and zero end-of-life gas recycling costs. Sourced through Funator (an Authorized Schneider Electric Partner), verified by authentic factory serial numbers, and backed by factory FAT witness testing.

 

Technical Specifications

Schneider GM AirSeT Technical Specifications
Rated Voltage Ur kV 12 17.5 24
Rated Short-Duration Power Frequency Withstand Voltage
Between phases, phase to earth Ud kV 28 38 50
Across the isolation distance Ud kV 32 45 60
Rated Lightning Impulse Withstand Voltage
Between phases, phase to earth Up kV 75 95 125
Across the isolation distance Up kV 85 110 145
Number of phases     3
Rated frequency fr Hz 50
Rated Values at 50 Hz
Busbars Ir A 1250
Circuit breaker cubicle, disconnector cubicle Ir A 630, 800, 1250
Rated short-time withstand current Ik kA 16, 20, 25
Rated duration of short circuit tk s 3
Rated peak withstand current Ip kA 40, 50, 63
Rated making current Ima kA 40, 50, 63
Rated short-circuit breaking current Isc kA 16, 20, 25
Insulating gas     Pure air
Rated filling pressure at +20 °C Pre MPa 0.12
Alarm pressure at +20 °C Pae MPa 0.11
Minimum functional pressure at +20 °C Pme MPa 0.10
Internal arc classification     IAC AFL
Rated arc fault current IA kA 16, 20, 25
Rated arc fault duration tA s 1
Partition class     PM
Loss of service continuity class     LSC2
Ambient air temperature     -25 °C to +40 °C
Installation altitude     1000 m
Rated Supply Voltage
Direct current voltage (DC) Ua V 24, 30, 48, 60, 110, 125, 220
Alternating current voltage (AC) Ua V 110, 120, 220, 230

 

Why choose Schneider GM AirSeT?

 Durability
GM AirSeT uses pure air for insulation and vacuum interrupters for current interruption. These components are housed in a sealed-for-life tank with an annual leakage rate below 0.1%. The three-position disconnector provides connected, disconnected and earthed positions. Combined with mechanisms designed for high mechanical and electrical endurance, this construction supports a service life of up to 40 years.

 Upgradeability
Digital functions can be upgraded on site to Active or Active Plus configurations. Additional cubicles can be installed at either end of the switchboard. Before extending the lineup, check busbar compatibility, available space, protection settings and the required shutdown procedure.

 Resource Efficiency
Pure air provides dielectric insulation inside the sealed tank; the vacuum interrupters handle switching arcs. No SF6 or alternative insulating gas mixture is required. Integrated sensors provide condition data to support maintenance planning and reduce unnecessary inspection visits.

 End-of-Life Management
Switching arcs remain inside the vacuum interrupters, preventing arc-related decomposition of the insulating air. The air does not require recovery or recycling and can be released during controlled decommissioning in accordance with the manufacturer’s procedures. The remaining components should be dismantled and sorted through the appropriate recycling routes.

 

Benefits of GM AirSeT

GM AirSeT: Schneider's SF₆-free primary GIS up to 36 kV. Pure air insulation, vacuum interruption, natively digital with embedded sensors. No on-site gas handling, compact sealed tank, 40-year lifespan for sustainable MV distribution.

Schneider Product Advantages

 

Certificate

Schneider Authorization Certificate

FAQ

 1. Does GM AirSeT use SF6 gas?
No. GM AirSeT uses pure air for insulation and vacuum technology for current interruption. It requires no SF6 or alternative insulating gas mixtures.

 2. What voltage and current ratings are available?
The version listed on this page supports 12, 17.5 and 24 kV, with busbar current up to 1250 A and short-time withstand current up to 25 kA for 3 seconds.

 3. Does the sealed tank require routine gas refilling?
The tank is sealed for life, with a specified annual leakage rate below 0.1%. Routine refilling is not required under normal operating conditions. Pressure alarms must be investigated according to the manufacturer’s instructions.

 4. Can the switchboard be expanded later?
Yes. Additional cubicles can be installed on either side. Extension requires confirmation of busbar compatibility, available installation space and the planned shutdown arrangement.

5. Can condition monitoring be added after installation?
Yes. Digital functions can be upgraded on site to Active or Active Plus configurations. Required sensors, communication equipment and compatibility depend on the existing configuration.

 6. What information do you need for a quotation?
Send your single-line diagram, voltage, current, fault level and panel quantities. Include protection requirements, site conditions and your delivery schedule so we can confirm the configuration and price.

Key Features

  • Internal arc classified (IAC) for operator safety
  • LSC2B service continuity — no outage for maintenance
  • Easergy smart-sensor ready for condition monitoring
  • Front-access cable compartment, compact footprint

Documentation

Catalogs, CAD drawings and manuals are free — leave your work email and we send the package within 12 hours.

Application Scenarios

Where GM AirSeT delivers — typical on-site installations across industries and regions.

Data center & buildings

01

Data center & buildings

Industrial

02

Industrial

Infrastructure

03

Infrastructure