01
Medium Voltage Switchgear
SF₆-free primary MV switchgear using pure air insulation and vacuum switching — future-proof for grids moving away from fluorinated gases.
Made to Order Schneider GM AirSeT Pure air insulation combined with vacuum interruption for primary distribution up to 36 kV. Zero greenhouse gas emissions (GWP < 1), full compliance with IEC 62271-200 type testing, and zero end-of-life gas recycling costs. Sourced through Funator (an Authorized Schneider Electric Partner), verified by authentic factory serial numbers, and backed by factory FAT witness testing.
| Rated Voltage | Ur | kV | 12 | 17.5 | 24 |
|---|---|---|---|---|---|
| Rated Short-Duration Power Frequency Withstand Voltage | |||||
| Between phases, phase to earth | Ud | kV | 28 | 38 | 50 |
| Across the isolation distance | Ud | kV | 32 | 45 | 60 |
| Rated Lightning Impulse Withstand Voltage | |||||
| Between phases, phase to earth | Up | kV | 75 | 95 | 125 |
| Across the isolation distance | Up | kV | 85 | 110 | 145 |
| Number of phases | 3 | ||||
| Rated frequency | fr | Hz | 50 | ||
| Rated Values at 50 Hz | |||||
| Busbars | Ir | A | 1250 | ||
| Circuit breaker cubicle, disconnector cubicle | Ir | A | 630, 800, 1250 | ||
| Rated short-time withstand current | Ik | kA | 16, 20, 25 | ||
| Rated duration of short circuit | tk | s | 3 | ||
| Rated peak withstand current | Ip | kA | 40, 50, 63 | ||
| Rated making current | Ima | kA | 40, 50, 63 | ||
| Rated short-circuit breaking current | Isc | kA | 16, 20, 25 | ||
| Insulating gas | Pure air | ||||
| Rated filling pressure at +20 °C | Pre | MPa | 0.12 | ||
| Alarm pressure at +20 °C | Pae | MPa | 0.11 | ||
| Minimum functional pressure at +20 °C | Pme | MPa | 0.10 | ||
| Internal arc classification | IAC AFL | ||||
| Rated arc fault current | IA | kA | 16, 20, 25 | ||
| Rated arc fault duration | tA | s | 1 | ||
| Partition class | PM | ||||
| Loss of service continuity class | LSC2 | ||||
| Ambient air temperature | -25 °C to +40 °C | ||||
| Installation altitude | 1000 m | ||||
| Rated Supply Voltage | |||||
| Direct current voltage (DC) | Ua | V | 24, 30, 48, 60, 110, 125, 220 | ||
| Alternating current voltage (AC) | Ua | V | 110, 120, 220, 230 | ||
Durability
GM AirSeT uses pure air for insulation and vacuum interrupters for current interruption. These components are housed in a sealed-for-life tank with an annual leakage rate below 0.1%. The three-position disconnector provides connected, disconnected and earthed positions. Combined with mechanisms designed for high mechanical and electrical endurance, this construction supports a service life of up to 40 years.
Upgradeability
Digital functions can be upgraded on site to Active or Active Plus configurations. Additional cubicles can be installed at either end of the switchboard. Before extending the lineup, check busbar compatibility, available space, protection settings and the required shutdown procedure.
Resource Efficiency
Pure air provides dielectric insulation inside the sealed tank; the vacuum interrupters handle switching arcs. No SF6 or alternative insulating gas mixture is required. Integrated sensors provide condition data to support maintenance planning and reduce unnecessary inspection visits.
End-of-Life Management
Switching arcs remain inside the vacuum interrupters, preventing arc-related decomposition of the insulating air. The air does not require recovery or recycling and can be released during controlled decommissioning in accordance with the manufacturer’s procedures. The remaining components should be dismantled and sorted through the appropriate recycling routes.


1. Does GM AirSeT use SF6 gas?
No. GM AirSeT uses pure air for insulation and vacuum technology for current interruption. It requires no SF6 or alternative insulating gas mixtures.
2. What voltage and current ratings are available?
The version listed on this page supports 12, 17.5 and 24 kV, with busbar current up to 1250 A and short-time withstand current up to 25 kA for 3 seconds.
3. Does the sealed tank require routine gas refilling?
The tank is sealed for life, with a specified annual leakage rate below 0.1%. Routine refilling is not required under normal operating conditions. Pressure alarms must be investigated according to the manufacturer’s instructions.
4. Can the switchboard be expanded later?
Yes. Additional cubicles can be installed on either side. Extension requires confirmation of busbar compatibility, available installation space and the planned shutdown arrangement.
5. Can condition monitoring be added after installation?
Yes. Digital functions can be upgraded on site to Active or Active Plus configurations. Required sensors, communication equipment and compatibility depend on the existing configuration.
6. What information do you need for a quotation?
Send your single-line diagram, voltage, current, fault level and panel quantities. Include protection requirements, site conditions and your delivery schedule so we can confirm the configuration and price.
Catalogs, CAD drawings and manuals are free — leave your work email and we send the package within 12 hours.
Where GM AirSeT delivers — typical on-site installations across industries and regions.