01
Ring Main Unit
Explore Schneider SM6 medium-voltage RMU switchgear up to 24kV/36kV. Compare technical specs, modular models, pros & cons, and international project applications.
In Stock Schneider SM6, also known as semi insulated ring main unit, is characterized by the core switch being sealed in SF6 gas, while busbars, cables, etc. are exposed to air, hence it is called semi insulated.And for fully insulated ring main units such as SafeRing and 8DJH, all live conductors are sealed inside the box. During the operation of the product, personnel cannot come into contact with the live conductors, which further ensures the safety of operators and maintenance personnel. So technically speaking, full insulation is more advanced, and currently semi insulated ring main unit products are no longer used in China.

Schneider SM6 switchgear internal structure operation view
Schneider launched the SM6 series modular ring main unit products as early as 1991. Initially, this Schneider SM6 only supported the highest SM6 24kV voltage level, commonly known as the SM6 24 Schneider in the industry. One product covered all voltage levels below 24kV. By 2010, there were already one million Sm6-24 Schneider units in operation.
But later on, it also expanded to 36kV products and launched the SM6 36 Schneider series, alongside 24kV products. If you need to obtain equipment operation and maintenance instructions, you can refer to the official Schneider SM6 manual for complete installation, debugging, and maintenance instructions.
1. Load switch and fuse combination unit
2. Circuit breaker and contactor unit
3. Metering&Sensing Unit
4. Busbar&Incomer Units
5. Auxiliary transformer and safety grounding unit
Busbars system: All busbars are located on the same horizontal plane, making it easy to expand switchgear or connect with existing equipment in the future.
The circuit breaker unit design of this Schneider Electric SM6 switchgear ensures operational stability:
The entire series of Schneider SM6 switchgear covers four core voltage levels, among which the core parameters of the largest market stock Sm6 24kV series and SM6 36 Schneider series are as follows:
| Technical Parameter | 12 kV Class | 17.5 kV Class | 24 kV Class (SM6-24) | 36 kV Class (SM6-36) |
|---|---|---|---|---|
| Rated Voltage | 12 kV | 17.5 kV | 24 kV | 36 kV |
| Power Frequency Withstand Voltage (1 min) | 28 kV | 38 kV | 50 kV | 70 kV |
| Power Frequency Withstand Voltage (across isolating gap) | 32 kV | 45 kV | 60 kV | 80 kV |
| Lightning Impulse Withstand Voltage (1.2/50µs) | 75 kV | 95 kV | 125 kV | 170 kV |
| Lightning Impulse Withstand Voltage (across isolating gap) | 85 kV | 110 kV | 145 kV | 195 kV |
| Rated Continuous Current (In) | 400 / 630 / 1250 A | 400 / 630 / 1250 A | 400 / 630 / 1250 A | 630 / 1250 A |
| Short-time Withstand Current | 12.5 / 16 / 20 / 25 kA | 12.5 / 16 / 20 / 25 kA | 12.5 / 16 / 20 / 25 kA | 12.5 / 25 kA |
| Circuit Breaker Short-circuit Breaking Capacity (Isc) | 20 / 25 kA | 20 / 25 kA | 20 / 25 kA | 20 kA |
Friendly Reminder:Available ratings and options depend on configuration. Contact us to confirm specifications for your project.
Schneider Electric SM6 is a very classic ring main unit product, commonly known in the industry as schneider electric sm6 switchgear / schneider sm6 switchgear, Until today, Indonesian PLN still insists on bidding for this type of ring main unit product, with the mainstream procurement model focused on the SM6 24 Schneider (Sm6 24kv), and there is also a stable demand for the SM6 36 Schneider.