Product Overview of Schneider PIX500 12kV Switchgear

Schneider Electric PIX500 is a 12kV air-insulated medium voltage switchgear designed for substations, industrial networks and transport infrastructure. It features a compact 500mm cabinet width, HVX vacuum circuit breaker and SGN12 three-position disconnector for reliable switching and electrical isolation.

The PIX500 supports main busbar currents up to 4000A, feeder currents up to 1250A and short-time withstand current of 31.5kA for 4 seconds. Its insulation ratings reach 42/48kV power-frequency withstand and 75/85kV lightning impulse withstand, depending on configuration.

With back-to-wall installation and front access, PIX500 helps optimize switchgear room space. Typical applications include tramway systems, tunnels, bridges, prefabricated substations and industrial power distribution. Final selection depends on the project single-line diagram and protection requirements.

Internal Structure of the Schneider PIX Series

Internal Structure of the Schneider PIX Series

Key Advantages of PIX500: Compact Design, Air Insulation and Vacuum Switching

1. SF6-Free Air Insulation

- Uses air as the primary insulating medium.
- Avoids the need for SF6 gas as the main insulation medium in the specified configuration.
- Reduces SF6-specific gas handling, leakage monitoring and recovery requirements.

2. Reliable Vacuum Arc Interruption

- Equipped with an HVX sealed vacuum circuit breaker.
- The switching arc is extinguished inside a sealed vacuum interrupter.
- Supports reliable switching and fault interruption under the specified operating conditions.

3. Compact 500mm Cabinet Design

- Cabinet width of only 500mm.
- Helps reduce electrical room footprint.
- Supports back-to-wall installation and front-side operation.

4. Three-Position Switching Safety

- Uses the SGN12 three-position disconnector.
- Provides connected, isolated and earthed positions.
- Mechanical and electrical interlocking helps prevent incorrect switching sequences.

5. High Electrical Withstand Performance

- Main busbar rated current up to 4000A.
- Short-time withstand current of 31.5kA for 4 seconds.
- Internal arc classification IAC AFLR, 31.5kA for 1 second.

6. Remote Operation Options

- HVX circuit breaker and SGN12 disconnector can be equipped with motorized operation.
- Supports remote switching when integrated with the appropriate control system.
- Helps reduce the need for operators to approach energized equipment.

Schneider PIX500 Technical Specifications and Electrical Ratings

Core Electrical Specifications
Rated Voltage 12 kV
Power Frequency Withstand Voltage 42 / 48 kV
Lightning Impulse Withstand Voltage 75 / 85 kV
Rated Main Busbar Current 4000 A
Rated Feeder Current 1250 A
Rated Short-Time Withstand Current 31.5 kA / 4 s
Internal Arc Classification IAC AFLR 31.5 kA / 1 s
Protection Degree IP4X, higher protection available as an option
Structure and Configuration
Cabinet Width 500 mm
Front Operating Clearance Approximately 1 m
Circuit Breaker HVX Fixed Vacuum Circuit Breaker
Disconnector SGN12 Three-Position Disconnector, Manual or Motorized Operation
Installation Method Back-to-Wall Installation
Main Circuit Connection Fixed Main Circuit Connection, Eliminating the Need for Traditional Draw-Out Operations During Maintenance

Note: Not sure if Schneider PIX500 12kV switchgear is suitable for your project? Send us your single-line diagram (SLD), technical specifications and electrical requirements. Our team will provide free technical selection support and a formal quotation within 24 business hours.

PIX500 Switchgear Configurations and HVX Vacuum Circuit Breaker Options

Available Panel Configurations of Schneider PIX500

1. Incoming Feeder Configuration
- HVX vacuum circuit breaker.
- SGN12 three-position disconnector.
- Current transformers and protection relays, according to the protection scheme.

2. Outgoing Feeder Configuration
- Feeder circuit breaker rated up to 1250 A.
- Cable-side connection and protection.
- Optional electrical operation and remote control.

3. Busbar Connection Configuration
- Main busbar rated up to 4000 A.
- Busbar connection and sectionalizing arrangements, subject to the approved system design.
- Coordinated short-circuit withstand ratings.

4. Motorized Operating Configuration
- Motorized HVX circuit breaker operation.
- Optional motorized SGN12 disconnector.
- Electrical interlocking and remote-control interfaces.

5. Protection and Monitoring Options
- Protection and control relays.
- Current transformers (CTs).
- Voltage transformers (VTs), where applicable.
- Voltage presence indication.
- Surge protection and auxiliary control devices, subject to design.

6. Project-Specific Engineering
- Incoming and outgoing cable arrangements.
- Auxiliary control voltage.
- Protection functions and communication interfaces.
- Applicable internal arc and enclosure protection requirements.

Where Is Schneider PIX500 Used? Key Industrial and Infrastructure Applications

1. Schneider PIX500 for Tramway Traction Power Distribution

Used in primary distribution systems supplying railway and tramway substations. The compact 500mm panel design helps optimize electrical room space in urban transportation infrastructure.

2. Schneider PIX500 for Bridge Electrical Infrastructure

Suitable for primary power distribution in bridge infrastructure projects, where compact switchgear arrangements and reliable feeder protection are required.

3. Schneider PIX500 for Tunnel Power Distribution

Used in tunnel electrical substations to distribute medium-voltage power to ventilation, lighting, drainage and auxiliary electrical systems.

4. Schneider PIX500 for Prefabricated Substations

Integrated into prefabricated substation systems for 12kV primary power receiving, switching and distribution. Its compact cabinet width helps optimize container and substation layouts.

5. Schneider PIX500 for Mobile Substations

Suitable for mobile power distribution installations where compact medium-voltage switchgear and flexible equipment arrangements are required.

6. Schneider PIX500 for Industrial Primary Distribution

Applicable to industrial primary distribution systems requiring 12kV incoming supply, feeder protection and busbar distribution.

Schneider PIX500 Mobile Substation Application Reference

Schneider PIX500 Mobile Substation Application Reference

Why Choose Funator for Schneider PIX500 Switchgear Supply?

Funator provides Schneider Electric equipment sourcing, technical coordination and international project supply services for medium-voltage power distribution applications.

1. Schneider Electric Brand Verification
We confirm the product model, manufacturing source, component identification and applicable brand authorization documents before order confirmation.

2. Accurate Technical Matching
We review the 12kV rating, 4000A main busbar, 1250A feeder rating, 31.5kA short-time withstand capacity, HVX breaker and SGN12 disconnector against your technical specification.

3. Project-Based Pricing
We prepare quotations according to panel quantity, switching components, protection devices, motorized operation and project-specific accessories. Itemized pricing is available upon request.

4. Confirmed Production Lead Time
We check component availability, manufacturing schedules and drawing approval status before confirming the estimated delivery date.

5. Project Reference Support
We can provide available product photographs, technical information and relevant application references for tender evaluations, subject to disclosure permission.

6. Pre-Shipment Inspection
We coordinate cabinet appearance inspection, nameplate verification, component model checks, quantity verification, wiring inspection and export packing checks.

7. Factory Acceptance Testing
Applicable factory tests can be arranged according to the manufacturer's procedures and project requirements. Witnessed FAT can be discussed before order confirmation.

8. Test Reports and Technical Documentation
Available documents may include product datasheets, approved drawings, wiring diagrams, routine test reports, applicable type-test reports and quality documentation.

Schneider PIX500 FAQs: Price, Delivery, Warranty and Technical Support

1. Is Schneider PIX500 suitable for a 12kV power distribution system?

Yes. PIX500 is designed for 12kV primary distribution and features a 4000A main busbar, 1250A feeder rating and 31.5kA short-time withstand current for 4 seconds.

2. What is the price of Schneider PIX500 switchgear?

Pricing depends on panel quantity, HVX breaker configuration, SGN12 disconnector operation, protection relays and accessories. Send your panel schedule for an itemized quotation.

3. What is the delivery time for PIX500?

Lead time depends on configuration, component availability and production scheduling. We confirm the estimated delivery date after technical approval and order confirmation.

4. Can PIX500 be supplied with motorized operation?

Yes. The HVX vacuum circuit breaker and SGN12 three-position disconnector can be equipped with optional motorized operation, subject to the selected configuration.

5. Can I inspect the PIX500 switchgear before shipment?

Yes. Pre-shipment inspection can cover cabinet appearance, nameplates, component models, wiring, accessories and packing. Factory acceptance testing can also be arranged according to the agreed inspection scope.

6. What technical documents and test reports are available?

Available documents may include datasheets, general arrangement drawings, wiring diagrams, routine test reports and applicable type-test reports. Specific certification requirements should be confirmed before ordering.

7. Do you provide international shipping for PIX500?

Yes. Sea freight, air freight and door-to-door delivery can be coordinated. FOB, CIF and DDP terms can be discussed according to the destination and customs requirements.

8. What warranty and after-sales support do you offer?

Warranty terms follow the manufacturer's policy and sales contract. Funator can coordinate technical troubleshooting, spare-parts enquiries and manufacturer communication after delivery.

Key Features

  • 500 mm Width; Up to 60% Space Saving
  • Air-Insulated Design with HVX Vacuum Circuit Breaker
  • IAC AFLR 31.5 kA / 1 s
  • Motorized Operation and Online Monitoring

Documentation

Catalogs, CAD drawings and manuals are free — leave your work email and we send the package within 12 hours.

Application Scenarios

Where PIX500 delivers — typical on-site installations across industries and regions.

Schneider PIX500 Mobile Substation Application Reference

01

Schneider PIX500 Mobile Substation Application Reference

Schneider PIX500 Tramway Traction Substation Application Reference

02

Schneider PIX500 Tramway Traction Substation Application Reference

Schneider PIX500 Tunnel Medium Voltage Power Distribution Reference

03

Schneider PIX500 Tunnel Medium Voltage Power Distribution Reference