Authorized Schneider GMA SeT Series GIS MV switchgear (24kV, 2500A, 31.5kA) with custom PowerLogic P3/P5 relay configuration for EPC, mining & BESS sites.
In Stock Schneider GMA MV Switchgear is part of Schneider’s SeT Series MV Switchgear, commonly referred to as Schneider GMA GIS Switchgear—a compact gas-insulated medium-voltage switchgear with a maximum rated voltage of 24 kV. All live parts of the main circuit are enclosed within a stainless steel sealed gas-insulated compartment. A vacuum arc extinguisher is responsible for breaking the circuit, while the sealing gas provides only phase-to-phase and phase-to-ground insulation and does not participate in arc extinction. The cabinet is divided into a gas-insulated main circuit compartment, a mechanical compartment, a secondary control compartment, and a cable compartment. It features a dual mechanical and electrical five-prevention interlock system, and fault arcs are vented in a rearward direction to ensure the safety of maintenance personnel working at the front of the cabinet.

The busbars are connected via inter-cabinet plug-in joints, eliminating the need for on-site fabrication of rigid busbars during cabinet assembly and resulting in a shorter installation cycle. The secondary protection circuits are natively compatible with Schneider Electric’s relay protection systems, enabling the implementation of a proven PowerLogic P3 P5 Switchgear protection solution. The entire set of protection parameter settings, communication configurations, and secondary power injection debugging can be delivered simultaneously. Compared to conventional air-insulated armored switchgear, Schneider GMA GIS Switchgear occupies less floor space and offers greater resistance to dust, condensation, and high-humidity, contaminated environments. Many overseas EPC projects prioritize this model; however, it is important to note that it features a permanently sealed design that does not require opening the enclosure for gas replenishment. Therefore, maintenance practices cannot be directly applied from standard GIS switchgear—this is the most common pitfall encountered on-site.
Challenge 1: Insufficient space in the switchgear room; existing substations cannot accommodate AIS air-insulated switchgear due to capacity limitations → Solution: Schneider GMA MV Switchgear, which is 25% smaller in volume than traditional GIS with the same specifications and features modular side-by-side expansion;
Challenge 2: High levels of condensation and dust at coastal, mining, and water treatment sites cause insulation components in air-insulated switchgear to accumulate contaminants and experience flashover → Solution: Schneider GMA GIS Switchgear features a fully sealed IP65 main circuit gas compartment, isolating live primary components from the external environment;
Challenge 3: Conventional GIS requires complex procedures for opening the cover to replenish gas and perform leak detection; overseas supervision and acceptance are stringent, and opening the cover voids the original manufacturer’s warranty → Solution: SeT Series MV Switchgear—this model features a “Sealed for Life” welded seal structure, and the standard configuration prohibits on-site opening of the cover for gas replenishment;
Challenge 4: Cumbersome commissioning of integrated protection systems; poor compatibility between different protection devices → Solution: Directly implement the PowerLogic P3 P5 Switchgear protection configuration, which features proven setting templates to significantly reduce on-site commissioning rework;
Pain Point 5: Risk of internal arcing and safety hazards during front-panel operation → Solution: Directional pressure relief structure with an AFL (R) 1s arc flash rating, ensuring pressure is not released toward the operating panel.
Request drawings, protection schematics and project quotation for this SeT Series MV Switchgear now, our electrical engineers will reply promptly.
Funator is familiar with the overseas project acceptance standards and key supervision checkpoints for the complete set of Schneider GMA MV Switchgear cabinets, helping you proactively avoid on-site risks related to cabinet assembly and interconnection, altitude-based selection, and protection configuration.We offer a turnkey delivery solution: supply of SeT Series MV Switchgear cabinets + pre-set PowerLogic P3 and P5 Switchgear protection systems, with protection logic, CT polarity, and arc flash parameter commissioning completed in-house to reduce on-site commissioning time.Prior to shipment, we conduct mechanical interlock cycle testing, random contact resistance inspections, and air pressure signal calibration; we simultaneously provide English test reports, nameplate documentation, and operation and maintenance guidelines to meet the requirements of overseas owners and supervisors in the Gulf and North Africa; we also support staggered shipments, spare parts provision, and remote technical support.

Schneider GMA GIS Switchgear installed in indoor substation, SeT Series MV Switchgear for compact distribution projects
A:Standard Schneider GMA MV Switchgear adopts sealed welded gas tank for SeT Series MV Switchgear, on-site opening and gas refilling are prohibited. Opening the tank will void the factory warranty. If low gas pressure alarm triggers, check sensor wiring and secondary circuit first. This is one of the most frequent on-site mistakes.
A:The cable compartment is narrow. Improper installation of arc light fiber probes will cause slow response. Wrong suppression logic setting may lead to fail-trip or false trip during secondary injection test, which often fails client inspection.
A:Not allowed. Misaligned contacts will cause overheating from high contact resistance. Never short the position feedback signal to energize the cabinet, overseas EPC inspectors will reject the whole panel.
A:When altitude>2000m, external insulation and alarm threshold must be revised. Using standard flatland parameters will usually cause withstand voltage test failure.
A:Forbidden. Grinding changes interlock travel, and may lead to closing earthing switch while circuit breaker is closed, a fatal safety hazard.
A:Different. Cable compartment inner space margin is limited. Terminals sized for normal AIS cabinet may be squeezed and damage insulation when closing the door. Confirm terminal outer diameter before order.
Catalogs, CAD drawings and manuals are free — leave your work email and we send the package within 12 hours.