Industry & Standards

BlokSeT vs Okken vs PrismaSeT: Which LV Switchboard for Your Project?

BlokSeT vs Okken vs PrismaSeT: Which LV Switchboard for Your Project?

PrismaSeT is a panel building system assembled by the panel manufacturer, with Schneider Electric supplying the enclosures, busbars (Linergy), and components. BlokSeT and Okken are type-tested switchboards delivered by Schneider Electric or its authorized manufacturers. Comparing the unit price of the former’s enclosures with the quoted prices for the complete switchboards of the latter two is meaningless, as they are not comparable.

PrismaSeT G: For input currents of 630 A or less, wall-mount installation is sufficient.

Input current up to 630 A, short-circuit withstand capacity (Isc) up to 50 kA, protection rating IP30–IP4X (the G-type model can achieve IP55), available in wall-mounted or floor-standing configurations. The system primarily features Acti9 and Compact NSX components, with circuits designed for lighting, outlets, and low-power loads. It is suitable for final distribution in commercial buildings, hotels, schools, clinics, and small workshops; wall-mounted installation eliminates the need for a structural foundation and a section of busbar routing.

PrismaSeT P, HD, 6300: Standardized Range Up to 4000 A

PrismaSeT P is rated up to 4,000 A on the input side and features Linergy busbars. Its functional units are primarily fixed-type and are not intended for motor control applications involving frequent operations. The HD model is the harsh-environment version (corrosion, dust) for the same current range, while PrismaSeT 6300 extends the system’s upper limit to 6,300 A. This range is selected because it involves moderate current levels, a large number of circuits, and sensitivity to installation costs.

PrismaSeT 3200 A switchgear bays and a single 4000 A switchgear cabinet at a project site in the United Arab Emirates

PrismaSeT 3200 A switchgear bays and a single 4000 A switchgear cabinet at a project site in the United Arab Emirates

BlokSeT: Below 7,000 A, Assembled from Standard Prefabricated Components

The cabinet is assembled from standard prefabricated components and is internally divided into busbar compartments, component compartments, and cable compartments. The compartmentalization complies with the requirements for “form of separation” specified in IEC 61439-2. The incoming current capacity is 7,000 A; for marine and offshore applications, the BlokSeT MB model supports up to 7,300 A. Cabinet width configurations can be calculated directly: a 600 mm-wide cabinet can accommodate 3 frame circuit breakers rated 800–1,600 A, or 2 rated 2,000–2,500 A, or 1 rated 3,200–4,000 A; For currents above 4,000 A, a 1,200 mm cabinet width is used, accommodating one MTZ3/MT unit. In a high-density configuration, a single cabinet can accommodate 24 circuits rated at 250 A or less.

BlokSeT General-Purpose (for transportation, service area, and airport projects)

BlokSeT General-Purpose (for transportation, service area, and airport projects)

BlokSeT Model Suffixes Determine Cabinet Configuration

Type D: Fixed power distribution; Type MX: Drawers or mixed configuration (withdrawable/mixed); Type DA: Dual-power-source switching (ATS); Type MS: Variable-frequency drive and soft starter; Type DC: Reactive power compensation; Type DP: Active filtering. There are only two draw-out configurations: FFF (fully fixed) and WWW (fully withdrawable); intermediate configurations are not available. The selection process involves first determining the suffix, then the cabinet width, and finally verifying the component layout.

Okken: Its drawer design and arc-resistant capabilities justify its price

Main busbars up to 7,300 A; PCC feeders and branch circuits up to 6,300 A; MCC conventional starters and soft starters up to 250 kW; and variable frequency drives up to 160 kW. Drawers are available in full-width and half-width configurations, with heights ranging from 100 to 600 mm. They plug directly into arc-free vertical busbars in 50-mm increments and can be racked in and out with the cabinet door closed (closed-door racking), featuring position indicators and mechanical interlocks. Enclosure classes include 2b/3b/4a/4b, with protection ratings of IP20/IP31/IP41/IP54; internal arc resistance is verified to 100 kA/0.5 s in accordance with IEC TR 61641, 3rd edition. Corrosion-resistant versions for SO₂ and H₂S, as well as seismic-resistant versions for 5G and 2.7G, are also available, with DNV, RINA, and BV maritime certifications and DEP Shell approval.

Okken switchgear bays at the Lukoil Neftochim Burgas refinery substation in Belgium

Okken switchgear bays at the Lukoil Neftochim Burgas refinery substation in Belgium

Criteria for Choosing Okken: Losses from Unplanned Outages Exceed the Price Difference for a Full Container Load

Data centers, petrochemical plants, rail transit, nuclear power plants, and heavy industries with continuous production fall into this category. The time saved by closing the drawer and switching back to Type 2 corresponds to operational maintenance time and downtime windows. Conversely, for projects where cabinet doors are rarely opened—even once every few years—and circuits primarily rely on fixed-type power distribution, the drawer’s capabilities go unused, and the extra cost yields no corresponding benefit.

Select Products Using a Four-Step Filtering Process; Do Not Base Your Choice Solely on Price

  • Filter by current and circuit type. For distribution circuits up to 630 A, select PrismaSeT G; for 1250–4000 A, select PrismaSeT P or BlokSeT D; for feeders, bus tie circuits, and grouped motor control circuits above 4000 A, select BlokSeT or Okken.
  • Filter by maintenance method. If live replacement of functional units is required, or if specifications mandate full withdrawal (WWW), BlokSeT can meet these requirements; however, Okken offers more detailed drawer specifications and finer interlocking precision.
  • Filter by installation environment. For environments with high humidity, sulfur, salt, dust, high altitude, or high seismic risk, select the corresponding version directly; do not retrofit standard switchgear. Retrofitted switchgear is not covered by type testing, and the corresponding reports cannot be issued during the acceptance phase.
  •  Filter by project specifications. If Okken is specified on the owner’s or general contractor’s shortlist of suppliers (vendor list), do not substitute it with a lower-priced alternative; the time cost of change order approval typically exceeds the price difference between the cabinets.

Medium-sized projects typically use a combination of different systems

For main distribution systems rated at 4,000 A or higher, Okken or BlokSeT is used in conjunction with busbars; BlokSeT D is used for workshop distribution; PrismaSeT G wall-mounted enclosures are used for offices and auxiliary buildings; and BlokSeT MS or Okken MCC is used in areas where motors are concentrated within process sections. When busbar routes can be connected to Canalis bus ducts, Okken provides the most direct interface with medium-voltage switchgear and bus ducts.

Providing the following five items when requesting a quote can reduce the need for back-and-forth confirmations

Inrush current and short-circuit current (including Icw requirements), the number of output circuits and the maximum current per circuit, whether a draw-out design is required and the form and rating, installation environment (altitude, ambient temperature, corrosion, vibration, protection rating), and applicable standards and certifications (IEC 61439-1/-2, CE, classification society, and owner’s shortlist). Once all five items are provided, the bill of materials (BOM) can be finalized correctly on the first attempt.

Supply and Documentation

Funator provides selection support and supply for Schneider Electric’s SeT Series authorized switchgear. We issue configuration lists, type test reports, and routine test reports tailored to each project, and support third-party inspection as well as CE and IEC 61439 documentation packages. Specifications are verified against the original manufacturer’s catalog; quotations are provided on an FOB or EXW basis; and technical inquiries are responded to within 24 hours.